Modern office building
Prime Electronics,Printable Electronics,Quantum Electronics Blog - computerwize.net

Common faults and analysis of electromagnetic flowmeter

Principle of Field Instrument Failure Analysis

Before analyzing field instrument failures, it is essential to have a thorough understanding of the production process, its conditions, and the relevant instrument system. This includes knowing the design intent, structure, characteristics, performance, and parameter requirements of the instrument system. Understanding these aspects helps in identifying the root cause of the failure more effectively.

Prior to inspecting an instrument system fault, it is important to gather information about changes in production load and raw material parameters from on-site operators. Reviewing the record curve of the faulty instrument allows for a comprehensive analysis to determine the underlying issue.

If the recorded curve is a dead line (a line with no change), or if it was previously fluctuating and suddenly becomes straight, it likely indicates a problem within the instrument system. Most modern recording instruments are DCS systems with high sensitivity. If changing process parameters does not result in any change in the curve, it suggests an issue with the instrument system. Conversely, if the curve responds normally, the instrument system is likely functioning correctly.

When process parameters change and the recorded curve shows abrupt jumps or reaches maximum values, the fault is often in the instrument system.

If the instrument record curve was normal before the fault occurred and then became irregular or the system became uncontrollable—even with manual operation—the issue may be related to the process operating system rather than the instrument itself.

When the DCS display meter is not working properly, checking the corresponding on-site indicator can help identify whether the instrument system has failed. If there is a significant difference between the two readings, the instrument system is likely at fault.

In summary, when analyzing field instrument failures, special attention should be given to changes in the characteristics of the controlled object and control valve. These could be the primary causes of the failure. Therefore, it is crucial to thoroughly examine both the field instrument system and the process operating system to identify the root cause.

Steps for Analyzing Flow Control System Failures

Summary of 414 Fault Handling Schemes for 24 Commonly Used Instruments and Meters...

1. Common Faults and Analysis of Electromagnetic Flowmeters

Serial NumberFault PhenomenonCause of IssueSolution
1After working for a period of time, the meter is not working properly.Is the power supply good?First check the external condition of the flowmeter; do not disassemble it blindly.
Whether the pipe leaksInspection and processing
In a non-full tube stateInspection and processing
Is there a bubble in the pipe?Inspection and processing
Is the signal cable damaged?Replace the new cable
Is the converter output signal open?Inspection and processing
2The signal becomes smaller or suddenly drops.The insulation between the electrodes is deteriorated or short-circuited, and there may be deposited dirt on the inner wall of the measuring tube.Should be cleaned and wiped the electrode.
Measuring catheter lining may be destroyedShould be replaced
Signal socket may be corrodedShould be cleaned or replaced
34 mA is output when the fluid in the measuring tube is stationary, and the current becomes small or zero when there is flow (debug during commissioning).When the flowmeter is installed, the flow direction is opposite to the actual flow direction.Check the flow direction of the flowmeter, change the installation direction, or exchange the X and Y wires in the converter.
Split type flowmeter A and B or X and Y lines have a set of reverseCarefully check the excitation and signal lines to correct errors on the wiring
4The flowmeter only outputs 4mA current (the split type wrong line mainly appears in the debugger).The measured medium does not actually flowTake corrective measures to ensure proper flow of media in the measuring tube
The excitation part of the converter is in the test stateInsert the shunt on 2, 3 or 3, 4 feet (working status)
The excitation line and signal line between the split type flowmeter sensor and the converter are connected incorrectly.When wiring properly, disconnected or shorted, contact the company if in doubt.
Sensor failureFaulty contact company
Converter excitation part circuit failureFaulty contact company
5The output signal is unstable (conductivity problem mainly occurs during the debugging period).The dielectric conductivity is lower than the lower limit of the electromagnetic flowmeter 5us/cmA medium with too low conductivity cannot be accurately measured with an electromagnetic flowmeter.
The medium contains solid particles or slurriesThe medium contains solid particles or slurries
Poor liquid or poor groundingThe insulated pipeline must be equipped with a grounding ring; the flowmeter must be reliably connected to the liquid through the grounding wire; the separate grounding can improve the anti-interference ability of the flowmeter.
External electromagnetic interference1. Keep away from interference sources; 2. Stray current is mainly grounded by good ground. It is best to ground it separately. Do not share grounding with other electrical appliances or instruments. 3. Split-type instrument signal line strengthens the shield, sets the iron pipe, or shields the wire to the other end.
Flowmeter measuring tube contains a lot of bubblesCheck the pipeline or valve, avoid introducing air into the fluid inlet; install the exhaust valve in a suitable place to eliminate the air in the measuring pipe section; install the flowmeter in a place where it is difficult to collect gas; open the exhaust pipe, downstream of the flowmeter can be raised appropriately
The fluid itself is fluctuating or pulsatingKeep the flowmeter away from the pulsation source as much as possible. If necessary, install a steady flow device at the appropriate position of the pipeline to minimize fluid stability.
There is liquid addition in the upstream main liquid, and it has not been mixed evenly at the flow meter.There is liquid addition in the upstream main liquid, and it has not been mixed evenly at the flow meter.
The flowmeter power supply line is parallel to the output signal line or worn in a conduitKeep the signal output lines from side by side with the AC power line, especially to avoid using the same line.
6Output signal super fullness valueThe actual flow rate is greater than the flowmeter full scale flow (overrange)Carefully analyze the pipeline, do not rely solely on the empirical value; sometimes the rated flow of the pump can not be used as the sole basis for the flow; properly close the flow to observe the flowmeter output. The commonly used flow exceeds the full scale of the flowmeter, you must contact the company to modify the range.
Split type flowmeter excitation, signal line connection errorCorrect the wrong wiring
Flowmeter measuring tube is not fullMake sure the flow meter is always full
Poor liquid or poor groundingThe insulated pipeline must be equipped with a grounding ring; the meter body must be reliably connected to the liquid through the grounding wire; the separate grounding can avoid the interference introduced by the grounding wire.
Converter failureConverter signal amplification, output part check, contact company
Sensor failureContact company
7The measurement result does not match the actual flow rate.Rear instrument matching problemCorrect flow and matching problems with the rear instrument or computer
The output signal line has a leakage (or a slight short circuit)Leakage of the current output signal will cause the indicated flow to be too small, and the signal line must be replaced.
Is the empirical 'actual flow' credible?Carefully analyze the flow and piping conditions, and seek to compare the reference frame when necessary, and contact the company if necessary.
Sensor installation is not standardizedStraight pipe section, full pipe condition, air bubbles, liquid pulsation, etc. According to the specification specification installation.
Electrode surface area scaleClean the sensor, taking care not to damage the lining
Process pipe leak or branch pipeEliminate valve leakage on the pipeline, branch shunting, etc.
Sensor insulation dropsContact the company

2. Common Faults and Analysis of Vortex Flowmeters

Serial NumberFault PhenomenonCause of IssueSolution
1Output signal when there is no flow after power-onInput shielding or poor grounding, introducing electromagnetic interferenceImprove shielding and grounding, and eliminate electromagnetic interference
The instrument is close to strong electrical equipment or high frequency pulse interference sourceKeep away from interference sources and take isolation measures to enhance power supply filtering
The pipeline has strong vibrationTake vibration reduction measures to enhance signal filtering and reduce amplifier sensitivity
Converter sensitivity is too highReduce sensitivity and increase trigger level
2No output signal after power-onPower failureCheck power and ground
Input signal line disconnectionCheck signal lines and terminals
A certain level of amplifier is faultyCheck the working point, check the components
Detecting original damageCheck sensor components and leads
No flow or too small flowCheck valve to increase flow or reduce pipe diameter
The pipe is blocked or the sensor is stuckCheck the cleaning pipe and clean the sensor
Vortex body scalingCleaning vortex generator
3Output signal is not stableStrong electrical interference signalStrengthen shielding and grounding
Sensor is contaminated or damp, sensitivity is reducedClean or replace the sensor to increase the gain of the booster
Sensor sensitivity is too highReduce the gain and increase the trigger level
Damaged sensor or poor lead contactCheck sensor and lead
Two-phase flow or pulsating flowStrengthen process management to eliminate two-phase flow or pulsating flow
Pipeline vibrationTake vibration reduction measures
Process instabilityAdjust the installation location
The sensor is installed with different hearts or gaskets protruding into the tubeCheck the installation and correct the inner diameter of the seal
Upstream and downstream valve disturbanceLengthen straight pipe or add flow regulator
Fluid is not filled with tubingChange the location and method of loading the flow sensor
Body wrapElimination of wraps
CavitationReduce flow rate and increase pressure inside the tube
4Large measurement errorInsufficient length of straight pipeLengthen straight pipe or add flow regulator
Analog conversion circuit zero drift or full scale adjustment is wrongCalibrate the zero and span scales
Supply voltage changes too muchCheck the power supply
The meter exceeds the verification periodTimely inspection
The difference between the inner diameter of the sensor and the pipe is largeCheck the inner diameter of the pipe and correct the meter factor
Install different hearts or seals into the tubeAdjust the installation, trim the gasket
Sensor contamination or damageCleaning replacement sensor
Two-phase flow or pulsating flowEliminate two-phase flow or pulsating flow
Pipe leakExclude leaks
5Measuring tube leakIn-tube pressure is too highAdjust tube pressure and change installation position
Nominal pressure selection is wrongUse high-grade nominal pressure sensor
Seal damageReplacement seal
Sensor is corrodedTake anti-corrosion and protection measures
6Abnormal whistling of the sensorThe flow rate is too high, causing strong vibrationAdjust flow or replace large gauges
CavitationAdjust flow and increase flow pressure
Body looseningFastening body
7Traffic accumulation counter does not workCounter wheel mechanism is not flexible or stuckCleaning the counter gear or replacing the counter
Counter coil offRewind the coil or replace the same spare part
Coefficient setting and programmer component circuit failureRepair the corresponding component circuit or replace the corresponding component
Display board front panel component circuit failureRepair the corresponding component circuit or replace the corresponding component
Vortex transmitter has no outputRepair or replace the transmission unit

3. Rotor Flowmeter Common Faults and Analysis

Serial NumberFault PhenomenonCause of IssueSolution
1Pointer jitterSlight pointer jitter, usually due to media fluctuationsCan be overcome by increasing the damping method
Moderate pointer jitter: usually due to media flow conditionsRegenerative or steady flow devices can be used to overcome or increase the rotor flowmeter damping
Violent pointer jitter: mainly due to medium pulsation, unstable air pressure or other operating conditions of the user, the pressure, temperature, flow rate and the actual state of the rotor flowmeter do not match, there is a big difference.Adjust the corresponding parameters
2The pointer stops at a certain position and does not moveOpen the valve too fast, causing the stopper to deform and the rotor to be stuckSlowly open the valve
The rotor guide rod is not the same as the stop ringThe instrument is removed, the deformed stopper is removed and shaped
3Large measurement errorInstallation does not meet the requirementsFor the vertical installation of the rotor flowmeter to maintain vertical, the inclination angle is not more than 20 degrees; for the horizontal installation of the rotor flowmeter to maintain horizontal, the inclination angle is not more than 20 degrees, the rotor flowmeter around 100mm space must not have ferromagnetic objects, the installation position should be away from the valve Diameter port, pump outlet, process line turning, etc. To maintain the front straight pipe section is 5D, the rear straight pipe section is required to be 250mm.
The density of the liquid medium changes greatlyThe density of the medium after the change can be brought into the formula, converted into an error correction coefficient, and then the flow measured by the flow meter is multiplied by the coefficient to be converted into a real flow.
Gas medium is greatly affected by temperature and pressureUse temperature and pressure compensation to get real flow
Long-term use and pipeline vibration and other factors cause the rotor flowmeter to sense the loosening of moving parts such as magnetic steel, hands, counterweights, and rotating magnetic steel, resulting in large errors.You can verify it by pushing the pointer with your hand. First press the pointer to the RP position to see if the output is 4 mA, whether the flow display is 0%, and then verify according to the scale. If the discrepancies are found, the parts can be adjusted. Generally require professional adjustment, otherwise it will cause the position to be lost, need to return to the manufacturer for correction.
4No current outputFirst look at the wiring is correctCorrect wiring
Whether the LCD has a display, if there is no output, there is mostly an output tube.Need to replace the circuit board
Missing calibration valueThe data recovery operation can be used. If it does not work, the data in the password 2000 can be set first, and then the data in the password 4011 can be set by manually pushing the pointer to calibrate the data from RP to 100%.
5No live displayCheck that the wiring is correctCorrect wiring
Check if the power supply is correctAdjust the power supply
LCD module check contact is not trueRe-install
For multi-wire power supply mode check 12, 13 terminals are connected to ammeter or short circuitRe-wiring
6On-site LCD always shows 0 or full scaleCheck the set range and zero point parameters in the 2000 password.Require ZERO to be less than the value of SPAN, the two values cannot be equal
Check if the sampled data is up, and push the pointer to see the sample value change. If there is no change, it is usually the line sampling circuit fault.Need to change the board
7The alarm is incorrectCheck the deviation setting d value can not be too largeAdjustment deviation setting
Is the logic function correct in the FUN function?HA-A represents the upper limit logic. LA-A represents the lower bound positive logic
Check the alarm value setting size in SUReset the alarm value in SU
If the LCD bar code indication is correct and the output is not active, check whether the negative pole of the external power supply and the external power supply is connected to the negative pole of the meter power supply.Adjust the power connection
Circuit board failureReplace the circuit board
8Cumulative pulse output is incorrectCheck if the alarm value of the selected cumulative pulse output is set to zero.Reset parameters
Circuit board failureReplace the circuit board

4. Common Faults and Analysis of Ultrasonic Flowmeters

Serial NumberFault PhenomenonCause of IssueSolution
1No characters without backlightInsurance tube blownDetermine the voltage level, check if the load is shorted or connected, and replace the fuse.
AC 220V voltage is not connectedPower on
The power module shuts off the power supply due to the protection actionTurn off the power and turn it back on.
2No flow display string bar graph shows normal1. Stop the pump; 2. Close the valve; 3. Connect with other pipes to form static water locally.1. Open the pump; 2. Open the valve; 3. Adjust the valve to change the partial pressure.
The flow rate in the pipe is less than the small flow rate cutoff valueCheck the small flow cutoff value and set it correctly
Zero calibration of current flow as zero due to misoperationZero calibration value clear
3No flow display, no bar graph display, status symbol "S" does not disappearThe actual installation distance of the sensor is too different from the installation distance of the meter display.Verify the meter input parameters and the actual installation distance of the sensor. Make the correct parameter entry and installation.
The signal is too weak to search1. Adjust the transducer and clean the dirt for the signal path with weak signal. 2. Exclude the pipeline gas, adjust the transducer for the weak signal path. 3. Modify the outer diameter of the pipe.
4Large flow deviationThe parameter input is incorrect, such as: pipe diameter, wall thickness, correction factor, etc.Enter the parameters correctly
The inside of the pipe is heavily fouled and the inner diameter becomes small.
5The flow display value fluctuates greatlyThe liquid contains a large amount of gas.1. Repair the leak point of the pipe network system; 2. Install an exhaust valve on the pipeline; 3. Install the switch point. (Judgement method: (a) A1, A2 value fluctuates greatly (b) Whether there is air sound in the pipe)
High suspended solids in liquidDoppler type ultrasonic flowmeter
Doppler type ultrasonic flowmeterChange point installation
Pipe fouling is serious, blocking sound wave transmission;Adjust the sensor insertion depth or remove the scale layer;
Sensor acoustic wedge surface scaling;Dial out the sensor, clean the wedge surface, reinstall
Sensor installed incorrectlyInstall the sensor correctly;
Sensor damageReplace the sensor;
Sensor cable and converter are not connectedReconnect;
Converter failureReplace the converter board
6Instantaneous and cumulative flow inconsistencyHost failureReplace the host

5. Common Faults and Analysis of Differential Pressure Flowmeters

Serial NumberFault PhenomenonCause of IssueSolution
1The indication is zero or the movement is smallThe balancing valve is not fully closed or leakedClose the balancing valve, repair or replace it
Throttle root high and low pressure valve is not openTurn on
Circulation device to differential pressure gauge valve, line blockageFlush the pipeline, repair or replace the valve
The steam pressure guiding tube is not completely condensedOpen the table after it is completely condensed
The gasket between the throttling device and the process pipe is not tightTighten the bolt or change the pad
Differential pressure gauge internal faultInspection, repair
2Indicating under zeroReverse high and low pressure pipelineCheck and connect properly
Signal line reverse connectionCheck and connect properly
The high pressure side pipeline is seriously leaking or crackingChange or change the pipe
3Low indicationHigh pressure side piping is not tightCheck and eliminate leaks
The balance valve is not tight or not closedCheck, close or repair
The air in the high pressure side pipeline is not drainedClean air
Differential pressure gauge or secondary instrument zero offset or displacementCheck and adjust
The throttling device and the differential pressure gauge are not matched and do not meet the design regulations.Replace the matching differential pressure gauge according to the design regulations
4High indicationLow pressure side piping is not tightCheck and eliminate leaks
Low-pressure side management of accumulated airClean air
The pressure of steam, etc. is lower than the design valueCorrect by actual density
Differential pressure gauge zero driftCheck and adjust
The throttling device and the differential pressure gauge are not matched and do not meet the design regulations.Replace the differential pressure gauge as required
5Ruler exceeds ruler limitActual flow exceeds design valueSwitch to the appropriate range of differential pressure gauge
Severe leakage on the low pressure side pipelineExclude leaks
Signal line has broken lineInspection, repair
6Indicates that the change is slow when the flow changesConnecting pipes and valves are blockedFlush the pipeline, dredge the valve
There is a fault inside the differential pressure gaugeCheck for exclusion
7Indicating large fluctuationsThe flow parameters themselves fluctuate too muchHigh and low pressure valves are properly closed
Load cell is sensitive to parameter fluctuationsAdjust the damping effect appropriately
8IndicationThe antifreeze facility fails, the differential pressure gauge and the hydraulic pressure in the pressure guiding tube are frozen.Strengthen the effect of antifreeze facilities
High and low pressure valves are not openOpen high and low pressure valve

6. Mass Flowmeter Common Faults and Analysis

Serial NumberFault PhenomenonCause of IssueSolution
1Instantaneous flow constant maximumTransmission signal cable is broken or sensor is damagedReplace the cable or replace the sensor
2Converter no displayPower failure, fuse burnoutCheck the power supply and replace the fuse
3No AC voltage but DC voltageMeasuring tube blockageDredge measuring tube
Installation stress is too largeRe-install
4Zero driftValve leakageExclude leaks
The calibration factor of the flowmeter is wrong.Check elimination
Damping too lowCheck elimination
Two-phase flowEliminate two-phase flow
Sensor junction box dampInspection, repair
Wiring failureCheck wiring
Ground FaultCheck ground
Installed with stressRe-install
Is there electromagnetic interference?Improve shielding and eliminate electromagnetic interference
5Display and output value fluctuationsLow dampingCheck damping
Drive amplifier instabilityCheck the driver amplifier
Density display value is unstableCheck density calibration factor
Wiring errorCheck wiring
Ground FaultCheck ground
Vibration interferenceEliminate vibration interference
Sensor pipe is blocked or has foulingCheck the cleaning pipe and clean the sensor
Two-phase flowEliminate two-phase flow
6Mass flow meter display is incorrectFlow calibration factor is wrongCheck calibration factor
Flow unit errorCheck flow unit
Zero errorZero adjustment
Flowmeter configuration errorReconfiguration
Incorrect density calibration factorCheck elimination
Wiring, ground faultCheck wiring, grounding
Two-phase flowEliminate two-phase flow
7Density display is incorrectIncorrect density calibration factorCheck elimination
Wiring, ground faultCheck wiring, grounding
Two-phase flow, slug flow vibration interferenceEliminate
Vibration interferenceEliminate
8There is no output from the power supplyElectricity failureCheck the power supply between the different terminals of the sensor
9Zero is stable but cannot return to zeroInstallation problemRe-install
The difference between fluid temperature, density and standard water is largerIncrease or decrease the zeroing resistance
Sensor measuring tube blockageDredge measuring tube

Cable Accessories

Cable Accessories,Performed Strain Clamp,Aluminium Alloy Preformed Guy Grip Dead End

Shahe Yipeng Import and Export trading Co., LTD , https://www.yppolelinehardware.com